Gebr. Nehl Holzindustrie in Bünde: over 2,000 modules in east-west orientation on a 9,000 m² renovated flat roof, more than half of the electricity used is for self-consumption.

Photovoltaics for the wood industry: 9,000 m² roof in Bünde

Photovoltaics for the wood industry almost always starts the same way: Gebr. Nehl Holzindustrie in Bünde-Bustedt had what many production companies have: a large flat roof that had been doing nothing for decades. Today, they are carrying over 9,000 m² of roof area with more than 2,000 photovoltaic modules, the , who up to 700,000 kWh per year produce. Over half of this is consumed directly by the company itself.

Faber Solartechnik implemented the project turnkey – from the roof renovation to the plant certification to the medium-voltage connection.

Project at a glance

Photovoltaics for the timber industry: Module area on the hall roof of Gebr. Nehl Holzindustrie in Bünde

  • over 9,000 m² covered roof area
  • over 2,000 modules in East-West orientation
  • 600 kW inverter output from 11 Sungrow devices
  • up to 700,000 kWh Annual revenue
  • more than 50 self- % consumption
  • Connection on Medium voltage level with its own transfer station
  • Assembly September 2019, connection to the grid February 2020

Why photovoltaic technology makes sense for the wood industry

Photovoltaics for the wood industry meets a favorable load profile. Wood processing runs in shifts and draws electricity evenly throughout the workday. This very load profile makes photovoltaic power generation attractive for a production operation: What is produced is used – if the system is properly designed.

The company wanted to reduce energy costs and establish its own power supply in the long term. A large, previously unused flat roof area was available.

What makes photovoltaic technology particularly suitable for the wood industry

The most important point in the project was not the size, but the orientation. A south-facing installation provides the highest midday peak – but exactly when a plant often cannot fully consume it. East-west distribution of generation spreads it over the morning and afternoon hours, thereby reducing energy consumption during peak work hours.

To this is added the area effect: an east-west flat roof is significantly denser because the module rows hardly shade each other. More power is generated from the same roof area. The result in Bünde: more than half of the generated electricity flows directly into production.

Technical implementation

Before construction began, the flat roof was completely renovated – a durable, long-lasting foundation is essential for an installation to operate uninterrupted for 25 years or more. Subsequently, the module area was created, powered by 11 inverters with a total of 600 kW: two Sungrow SG40CX, two SG50CX and seven SG60KTL.

The system feeds power at medium voltage level via its own substation. For this, an installation certificate type B according to VDE-AR-N 4110 was required, which fully meets the system’s requirements. A meteocontrol blue’Log XC takes care of the system control, while the network and system protection is handled by a Woodward MCA4.

Scope of delivery

  • Design and economic calculation
  • Renovation of the flat roof as a viable base
  • Planning, Statics and Assembly of the East-West System
  • Medium-voltage connection with transfer station
  • System certification type B according to VDE-AR-N 4110
  • Commissioning, monitoring and documentation

Result

Since February 2020, the system has been online. The installation itself was completed in September 2019 – a few months passed from the start of construction to the finished system. Today, the system covers a significant portion of its electricity needs itself.

Each facility is publicly registered

Photovoltaics for the wood industry is mandatory in Germany: Every production facility is registered. Market data register of the Federal Network Agency. We will take over the registration as part of the project.

Are you planning on using photovoltaic technology for the wood industry?

Then the question arises: how much of that can be attributed to your own consumption? We calculate this based on your load profile data. Contact us.

Frequently Asked Questions

East-West distribution of production is spread over the morning and afternoon instead of concentrated at a peak in the middle of the day, and flat roofs are arranged more densely. In Bünde, this means that more than half of the generated electricity is consumed directly on-site. For businesses with continuous daily consumption, this is usually the more economical design option.

If the remaining lifespan of the roof covering is shorter than the lifespan of the system, yes – otherwise modules have to be installed later. In Bünde, the flat roof was previously completely renovated. Whether this is necessary in your case will be determined by a roof assessment before planning.

It indicates that a generation facility meets the VDE-AR-N 4110 standard for medium-voltage connection. It becomes necessary as soon as a facility no longer feeds into the low-voltage grid. The facility in Bünde with a connection output of 0.749 MVA has passed this certification – we will handle the process for you.

Wood processing draws electricity evenly throughout the working day, and this profile fits well with the generation curve of an East-West plant. The plant in Bünde generates up to 700,000 kWh per year. How much of this your plant can take up depends on your load profile data.

In Bünde, the installation was completed in September 2019; in February 2020, the system went online. The construction itself is the planned part; the duration until connection to the grid is additionally dependent on certification and the grid operator.